FACP-6000-1AB火災(zāi)報(bào)警控制器(壁掛聯(lián)動(dòng)型)
主要技術(shù)特性
電源:
交流電源(主電源):額定工作電壓 ~220V (187~242V)
備用電源:根據(jù)不同點(diǎn)數(shù),應(yīng)配置不同容量的備用電源。
使用環(huán)境:
溫 度: 0℃~+42℃
相對(duì)濕度:≤95%,不凝露
容量:壁掛型、回路數(shù): 2個(gè)回路 回路地址的最大用量:242點(diǎn)
顯示器:LCD液晶屏
外形尺寸:(長*寬*高)470mm*130mm*420mm
布線要求:
·485通訊線和報(bào)警總線最好使用雙絞線RVS2×1.0㎜2或RVS2×1.5㎜2,當(dāng)環(huán)境干擾比較大時(shí),485通訊線應(yīng)考慮使用RVSP2×1.0㎜2的雙絞屏蔽線
·絕對(duì)不可將485通訊線和電話線與報(bào)警總線布在同一根多芯電纜中。
FACP-6000-1AB fire alarm controller (wall-mounted intermodal)
Main technical characteristics
Power supply:
Ac power (main power supply) : rated working voltage ~ 220V (187 ~ 242V)
Standby power supply: according to different points, alternate power sources should be equipped with different capacities.
Use environment:
The temperature: 0 ℃ ~ 42 ℃
Relative humidity: no more than 95%, no condensation
Capacity: wall hanging type, return number: the maximum amount of two loop return addresses: 242 points
Monitor: LCD LCD screen
Dimensions: (long * wide * height) 470mm * 130mm * 420mm
Wiring requirements:
· 485 communication line and alarm bus it is best to use twisted-pair RVS2 x 2 or 1.0 ㎜ RVS2 x 1.5 ㎜ 2, when the environment is larger, 485 communication line should consider using RVSP2 x 1.0 ㎜ 2 twisted-pair shielded wire
· no 485 communication line and telephone line and alarm bus are not in the same multi-core cable.